Magnetic Circuit Breakers, C Series

$26.000 - $300.000
SKU:
ECA
Grand Total:
26
Add to Custom Catalog

Related Products

Product Description

banner-template-spec-sheet.jpg

Manufacturer Carling
Type of Breaker Magnetic / Hydraulic Breaker
Breaker Series C series
Number of Poles Single or Multiple
Number of Throws              Single or Multiple
Percentage Overload vs. Trip Time in Seconds at +25°C (Vertical Mount)                
Delay 100% 135% 150% 200% 400% 600% 800% 1000%
DC 50/60-Hz Medium No Trip 6.5 - 115 3 - 65 1.2 - 20 0.08 - 3 0.018 - 2.5 0.015 - 0.8 0.009 - 0.25
"A" Series Interrupting Capacity (AMPS)        
Max Rating Voltage Frequency Phase Current Rating
Full Load Amps
Interrupting Capacity
UL/CSA (W/O backup fuse)
80 DC - 0.02 - 70 7500
65 DC - 71 - 100 5000
125/250 50/60 Hz 0.02 - 50 3000
125/250 50/60 Hz 31 - 50 2000

C-series Magnetic circuit breakers are affected strictly by current. This means that they are not affected by temperature as other breakers may be. C-series breakers cannot be forcibly held on. As the current exceeds the amount specified by the breaker, the circuit will then open. This is one of the many reasons that these breakers are so popular. Look at the chart above to see the interrupting capacity. Selecting the correct magnetic breaker for your application is not an easy task. Contact a Pacer expert today.



Applications:

  • Marine
  • Generators
  • Renewable Energy Systems

Features:

  • "Trip free"
  • Magnetic operation, operates as a function only of current
  • Panel-mounted
  • Power switching round cutout has a diameter of 0.63"

Technical Information:

  • Series Trip: Long delay
  • Inrush pulse tolerance: 12 times rated current
  • Operating Temp: -40°C to 85°C
  • Shock: Withstands 100 g or more without tripping while carrying full rated current in Mil-Std-202, Method 213.
  • Vibration: Withstands 10 g without tripping while carrying full rated current per Mil-Std-202, Method 204.
  • Endurance: Per UL 1077 (6000 operations at rated load plus 4000 operations with no load). Tested at a maximum rate of 6 times per minute.
  • Moisture Resistance: Meets requirements of Mil-C-55629, tested in accordance with Mil-Std-202, Method 106.
  • Salt Spray: Meets requirements of Mil-C-55629, tested in accordance with Mil-Std-202, Method 101.
  • Trip Free: Trips on overload and cannot be forcibly held on or restrained.